Jeffry April 16, 2019 for Model Number Whirlpool EV171NYMQ02 Upright Freezer I have a freezer that keeps building up ice on the coils. I changed the seal, the fan motor is working, it cools but I am thinking the auto defrost is working properly. I was thinking the WP4387501 Bimetal-Def might be my issue. It was replaced once before?
1 Answer Hello Jeffry, The defrost bi-metal WP4387501 could be the issue but this design normally has a failed defrost heater assembly W11175809. Read More...
Jack April 17, 2015 for Model Number Kenmore 675-28013-om The drain hole keeps freezing close. The defrost thermostat , the heater, the timer are all working ok. Is the defrost thermostat to blame that it would stay closed to long or not long enough? It still has the old defrost thermostat, part number 1-80251-101
1 Answer Hello Jack, I would change the defrost thermostat and chase the drain with a piece of weedeater line to ensure no obstructions are present. Read More...
Stu September 02, 2013 for Model Number Maytag MQF1656TEW01 (frost-free freezer) This freezer gets to around 26º F during the defrost cycles. Does this indicate a problem with the bimetal sensor? The timer was replaced under warranty (out of warranty now) when it was not getting below about 30º F at all. Now it gets to 0º F but then cycles through the higher temps in the mid 20s. I am afraid that this is too warm to be safe for frozen food.
1 Answer Hello Stu, You need to make sure the condenser coils, (hot coils), are not obstructed by lint or any other objects that can prevent air flow, (like paper bags, boxes, etc.). You should also check the frost pattern on the evaporator coils (cold coils). The frost on the cold coils should form at least 3/4 of the way down from the top of them. If the frost on the top is thick at the top, it is usually an evaporator fan motor issue. If there is no frost at the bottom at all or there is an ice ball where the lines come into the compartment, there is most likely a sealed system issue. Read More...